Product Description
Model NO.: DSS168
Installation: Direct Connected
Electric Equipment: Two Phase
Power Meter Connection: Terminal
Type: Energy Meter
Customized: Customized
Trademark: CALIN
Origin: Shenzhen China
Display: Digital
Usage: Multi-Functional Energy Meter, Watt-Hour Meter, Meter for Industry and Home Use, Standard Electric Energy Meter, Multi-rate Watt-hour Meters, Maximum Demand Meter
Theory:
Electronic Meter Measured Signal: Pulse Peak
Certification: RoHS, ISO, CE
Connection: Two Phase Three Wire
Specification: 120V/240V
Main Features
Energy Measurement
Total and time-sharing forward active & reactive energy measurement
Total and time-sharing reverse active & reactive energy measurement
Total forward & reverse apparent energy measurement
Save last one to sixteen months energy data
Max. Demand Measurement
Measure total and time-sharing forward active & reactive maximum demand and time of occurred
Measure total and time-sharing reverse active & reactive maximum demand and time of occurred
Measure total forward & reverse apparent maximum demand and time of occurred
Real Time Measurement
Real-time measurement of the phase voltage, current, total active power, reactive power, apparent power, total power factor, power grid frequency
TOU
4tariffs, 100holidays, 14seasontables, 8time zonetables, each table on maximum 14 time zones
Optical port interface
Support IEC62056-21 protocol
LCD display
Number of digits value field Up to 8
Digit size 6x14.5mm
Technical parameters:
Electrical parameters: |
Voltage |
Nominal voltage Un | 120/240V |
Extended operating voltage range | 80%~115%Un |
Limited voltage | 70%~120%Un |
Frequency | |
Nominal frequency fn | 60Hz |
tolerance | 5% |
Current | |
Basic current(Ib) | 10A |
Maximum current(Imax) | 100A |
Starting current(Ist) | 30mA |
Active energy constant | 400imp/kWh |
Measurement Accuracy | |
Active energy to IEC6205321 | Class1.0 |
Reactive energy to IEC6205323 | Class2.0 |
Power Consumption | |
Power consumption in Voltage circuit | <2W <8VA |
Power consumption in current circuit | <1VA |
Temperature range | |
Operation meter | 25ºC to+70ºC |
Storage | 40ºC to+85ºC |
|
Insulation strength |
AC Insulation strength | 4kV at 50Hz during 1min |
Impulse voltage 1.2/50μs mains connections | 8kV |
| |
Electro Magnetic Compatibility |
Electrostatic discharges | |
Contact discharge | 8kV |
Air discharge | 16kV |
Electromagnetic RF fields | |
27MHz to 500MHz typical | 10V/m |
100kHz to 1GHz typical | 30V/m |
Fast transient burst test | 4kV |
| |
Mechanical requirements | |
Meter shell Protection Rate | IP54 |
Protection | classII |
Contact us if you need more details on Two Phase Meter. We are ready to answer your questions on packaging, logistics, certification or any other aspects about Electricity Meter、Electronic Meter. If these products fail to match your need, please contact us and we would like to provide relevant information.